| Approvals/certifications | Certified to EN54-7 by Intertek (0359-CPR-00183). | 
| Application/operation | Uses an IR light source & photodiode to detect smoke. Typically used in escape routes, living areas, bedrooms & other enclosed spaces. Particularly effective at detecting slow burning fires caused by overheated electrical wiring or smouldering materials. | 
| Application temperature | n/a. | 
| Static response temperature | n/a. | 
| Sensitivity | Nominal alarm threshold of 0.16db/m obscuration measured in accordance with EN54-7:2000. | 
| Supply wiring | 2-wire monitored, polarity sensitive. | 
| Supply/operating voltage | 9 to 33V DC. | 
| Quiescent current | 30µA @ 24 VDC. | 
| Alarm voltage | 6-33V DC. | 
| Alarm current | 19mA @ 12-33V DC; 11mA @ 9V DC; 2.5mA@ 6V DC. | 
| Alarm reset voltage | Less than 1V DC (+0.5 seconds alarm reset time). | 
| Expansion connections | Remote LED output available via ActiV base. Current source to the negative line, short-circuit protected. Max voltage 2.7V DC. | 
| Product dimensions (mm) | 102.2mm diameter x 37mm deep (detector in base); 102.2mm diameter x 57.5mm deep. | 
| Construction & finish | White polycarbonate casing rated to UL94 V-2 with nylon parts. | 
| IP Rating | IP42. | 
| Weight | 99g. | 
 
Reviews