Series TY-FRB

Upright and Pendent Intermediate Level Sprinklers

Quick Response, K-factor=5.6

Features:

  • Factory assembled unit having an integral water shield
  • Intermediate Level Sprinklers are primarily designed for use in rack storage sprinkler systems where their thermally sensitive elements must be shielded from the water spray of higher elevation sprinklers that could operate earlier during a fire
  • May also used in other applications such as beneath open gridded catwalks

Hazard: Storage

Temperature: 135, 155, 175, 200, 286

Thread: 1/2″

Approval: UL, C-UL, FM

Response: Quick Response

SIN Numbers: TY313,TY323

Wrench: W6

Model ESFR-14

14.0 K-factor Pendent Sprinklers Early

Suppression, Fast Response

Features:

  • TYCO Model ESFR-14, 14.0 K-factor, Pendent Sprinklers (TY6236) are Early Suppression, Fast Response (ESFR) sprinklers having a nominal K-factor of 14.0.
  • They are suppression-mode sprinklers that are especially advantageous as a means of eliminating the use of in-rack sprinklers when protecting high-piled storage.
  • Model ESFR-14 Sprinklers are primarily designed for protection of the following storage arrangements: most encapsulated or non-encapsulated common materials including cartoned, unexpanded plastics & some storage arrangements of rubber tires, roll paper, flammable liquids

Hazard: Storage

Temperature: 155, 200

Thread: 3/4″

Approval: UL, C-UL, FM

Response: FR

SIN Numbers: TY6236

Wrench: W2

Model ESFR-17

Early Suppression, Fast Response Pendent

Sprinklers 16.8 K-factor

Features:

  • TYCO Model ESFR-17 Pendent Sprinklers are Early Suppression, Fast Response sprinklers having a nominal K-factor of 16.8
  • They are suppression mode sprinklers that are especially advantageous as a means of eliminating in-rack sprinklers when protecting high-piled storage.
  • The Model ESFR-17 Pendent Sprinklers provide the system designer with hydraulic and sprinkler placement options not presently available to traditional ESFR Sprinklers having a nominal K-factor of 14.0.

Hazard: Storage

Temperature: 165, 212

Thread: 3/4″

Approval: UL, C-UL, FM

Response: FR

SIN Numbers: TY7223

Wrench: W2, W30

Model ESFR-17

Early Suppression, Fast Response

Upright Sprinklers, K-factor=16.8

Features:

  • Early Suppression, Fast Response(ESFR)
  • Primarily designed for use in ceiling only sprinkler systems
  • Use of this sprinkler is especially advantageous as a means of eliminating the use of in-rack sprinklers when protecting rack storage arrangements
  • Unique, upright design and large K Factor overcome many pendent obstruction problems

Hazard: Storage

Temperature: 165, 212

Thread: 3/4″

Approval: FM, CE

Response: FR

SIN Numbers: TY7126

Wrench: W21

Model ESFR-25

Early Suppression, Fast Response

Pendent Sprinklers, K-factor=25.2

Features:

  • Early Suppression, Fast Response (ESFR)
  • Suppression-mode sprinklers that are especially advantageous as a means of eliminating the use of in-rack sprinklers when protecting high-piled storage
  • The TYCO Model ESFR-25 Pendent
  • Sprinklers are listed by UL for Specific Applications with a ceiling height greater than 45 ft. (13,7 m) up to and including 48 ft. (14,6 m), and a storage arrangement up to and including 43 ft. (13,1 m)
  • Direct attack on burning fuel by improved heavy sprinkler discharge
  • Patented frame design substantially reduces the frame shadow effects that often produce non-uniformity in spray pattern
  • Novel orifice seal and unique fast response link design are the very latest in sprinkler technology

Hazard: Storage

Temperature: 165, 212

Thread: 1″

Approval: UL, C-UL, FM, NYC, LPCB,

VdS, CE

Response: FR

SIN Numbers: TY9226

Wrench: W1

RAPID RESPONSE Series LFII Residential Sprinklers

Pendent Wet Pipe and Dry Pipe Systems, K-factor=4.9

Features:

  • Intended for use in the following scenarios:
  • Wet and dry pipe residential sprinkler systems for one/two-family dwellings and mobile homes per NFPA 13D
  • Wet and dry pipe residential occupancies up to and including four stories in height per NFPA 13R
  • Wet and dry pipe sprinkler systems for the residential portions of any occupancy per NFPA 13
  • Approved for special applications with beamed ceilings

Hazard: Wet or Dry

Temperature: 155, 175

Thread: 1/2″

Approval: UL, C-UL, NSF

Response: FR

SIN Numbers: TY2234

Wrench: W6

Wrench [Recessed]: W7

Series DS-1 Dry-Type Sprinklers

Pendent, Upright, and Horizontal Sidewall

Standard Response, Standard Coverage, K-factor=5.6K

Features:

  • Standard coverage
  • All hazards (light hazards, horizontal sidewall)
  • Lengths up to 48″ (1220 mm)
  • Designed for use in applications where sprinklers and/or connecting piping may be exposed to freezing conditions, or the sprinkler system is seasonally drained
  • Special assembly provides a seal at the main pipe to prevent water from entering the assembly until the sprinkler operates
  • Designed for use in applications requiring dry sprinklers, or where building construction or aesthetic considerations make the installation of dry horizontal sidewall sprinklers more desirable than the dry pendent type

Hazard: All,Light Hazard/Ordinary Hazard

Temperature: 135, 155, 175, 200,

286, 360

Thread: 1″

Approval: UL, C-UL, FM, NYC, LPCB,

CE, VdS

Response: Standard Response

SIN Numbers: TY3155,TY3255,TY3355

Wrench: Pipe Wrench

Wrench [Recessed]: ,W7

Series DS-1 Dry-Type Sprinklers

Pendent, Upright, and Horizontal Sidewall

Quick Response, Standard Coverage, K-factor=5.6K

Features:

  • Light hazard/Ordinary hazard
  • Lengths to 48″ (1220 mm)
  • Designed for use in applications where sprinklers and/or connecting piping may be exposed to freezing  conditions, or the sprinkler system is seasonally drained
  • Special assembly provides a seal at the main pipe to prevent water from entering the assembly until the sprinkler operates
  • Designed for use in applications requiring dry sprinklers, or where building construction or aesthetic considerations make the installation of dry horizontal sidewall sprinklers more desirable than the dry pendent type

Hazard: All,Light Hazard/Ordinary Hazard

Temperature: 135, 155, 175, 200, 286

Thread: 3/4″,1″

Approval: UL, C-UL, FM, NYC

Response: Quick Response

SIN Numbers: TY3935,TY3735,TY3135,TY3235,TY3335

Wrench: Pipe Wrench

Wrench [Recessed]: W7,

Model ESFR-17

Dry Type Pendent Sprinklers

Early Suppression Fast Response 16.8 K-factor

Features:

  • Early Suppression, Fast Response (ESFR)
  • The Model ESFR-17 Dry Type Sprinklers are primarily used for ceiling only sprinkler protection and used to protect solid piled, palletized, and rack storage that is subject to freezing temperatures
  • Suppression mode sprinklers that are especially advantageous as a means of eliminating in-rack sprinklers when protecting high-piled box-in-box refrigerated storage areas
  • The drop between the inlet and sprinkler remains dry until the sprinkler operates, allowing for a pendent sprinkler installation on a wet pipe sprinkler system where the dry drop and sprinkler are located in an area subjected to freezing temperatures
  • Eliminates in-rack sprinklers for box-in-box applications
  • The Model ESFR-17 Dry Type Pendent Sprinkler is FM Approved and has successfully undergone full-scale fire testing at FM Global, when used in conformance with applicable FM Global Property Loss Prevention Data Sheets.
  • Less costly to install and maintain than pre-action or antifreeze systems


Hazard: Storage

Temperature: 165, 212

Thread: 1-1/4″

Approval: UL, FM

Response: FR

SIN Numbers: TY7229

Wrench: W26

Series TY-B & TY-FRB

Sprinklers Alternate Materials of Construction

Stainless Steel, SMO, and Titanium

Features:

  • TY-B: 5 mm diameter heat sensitive glass bulb, standard response
  • TY-FRB: 3 mm diameter heat sensitive glass bulb, quick response
  • Corrosion resistant, standard coverage spray sprinklers designed for use in commercial occupancies where corrosive atmospheres may exist
  • Alternate materials of construction (Stainless Steel, SMO, or Titanium) are utilized to extend the life of a sprinkler beyond that which might be expected of copper alloy sprinklers exposed to corrosive atmospheres
  • (SMO = stainless-molybdenum alloyed)

Hazard: All

Temperature: 135, 155, 175, 200,

286, 360

Thread: 1/2″,3/4″

Approval: UL, C-UL, LPCB,

Lloyds,LPCB

Response: Standard Response,Quick