| Approvals/certifications |
Certified to EN54-5 by Intertek (0359-CPR-00183). |
| Application/operation |
Generates an alarm condition when it detects a temperature of between 69ºC & 85ºC. |
| Application temperature |
40°C typical, 65°C max. |
| Static response temperature |
69°C typical, 85°C max. |
| Supply wiring |
2-wire monitored, polarity sensitive. |
| Supply/operating voltage |
9 to 33V DC. |
| Quiescent current |
30µA @ 24 VDC. |
| Alarm voltage |
6-33V DC. |
| Alarm current |
19mA @ 12-33V DC; 11mA @ 9V DC; 2.5mA@ 6V DC. |
| Alarm reset voltage |
Less than 1V DC (+0.5 seconds alarm reset time). |
| Expansion connections |
Remote LED output available via ActiV base. Current source to the negative line, short-circuit protected. Max voltage 2.7V DC. |
| Product dimensions (mm) |
102.2mm diameter x 37mm deep (detector in base); 102.2mm diameter x 57.5mm deep. |
| Construction & finish |
White polycarbonate casing rated to UL94 V-2 with nylon parts. |
| IP Rating |
IP42. |
| Weight |
99g. |
Reviews